TM24415C
GE* Actual product may vary from image
Main breaker load centers arrive with a main breaker installed for a convenient and swift install. Main breakers allow for the user to stop the flow of electricity in the load center, shutting off all the power in the residence. The TM24415CB features spaces for 24, 1" breakers, a 150A main ampere rating, 3 phases, a bottom feed, and a combination/flush enclosure.
Details
MFG PART #:TM24415C
McMc Part #:GEDITM24415C
UPC #:783164189988
Inventory
$3,047.49 E
Details
MFG PART #:TM24415C
McMc Part #:GEDITM24415C
UPC #:783164189988
Inventory
Attributes
Features
Documentation
Attributes
Brand:GE
Type:3-Phase Standard
Voltage Rating:208Y/120 VAC
Amperage Rating:150 A
Number of Poles:1
Interrupt Rating:22 kA
Number of Circuits:24
Breaker Type:THQL
Wiring Configuration:4-Wire
Number of Spaces:36
Wire Size:1 to 3/0 AWG, 3/0 to 2/0 AWG
Mounting Type:Flush
Enclosure Type:NEMA 1
Enclosure Box Size:NEMA 11
Dimensions:33-3/16 in H x 14 in W x 3-3/4 in D
Features
Suitable for use as service entrance equipment when installed in accordance with the national electrical Code® |
6 to 42 circuit devices UL listed for bottom mounted lug by installing complete unit box, interior and front upside down |
60 to 70 deg C conductor rating |
Main lug models field convertible to main breaker |
Split neutrals extend the full length of the interior for ease of wiring |
Entire main lug line converts easily to main breaker |
Front packed in inner carton for added protection |
Straight through main wiring |
Compact box maintains optimum wire bending space |
Top feed |