EY50A
O-Z/Gedney* Actual product may vary from image
Explosionproof Conduit Sealing Fitting, Turning Radius 1-15/16 Inch, Trade Size 1/2 Inch, Connection Type Female, Female, Material Copper-Free Aluminum, Mounting Position Vertical, Enclosure Class I Div 1 and 2 Group C D, Class I Zone 1 and 2 Group IIA IIB, Class II Div 1 and 2 Group E F G, Class III, Approval UL, CSA, Overall Length 2-3/4 Inch, Application Seal Conduits in Vertical or Horizontal, to Minimize the Passage of Gases and Vapors and Prevent the Passage of Flames from One Portion of the Electrical System to Another Through the Conduit, Constructional Feature Explosionproof
Details
MFG PART #:EY50A
McMc Part #:EGSMEY50A
UPC #:783126056730
Inventory
$36.49 E
Details
MFG PART #:EY50A
McMc Part #:EGSMEY50A
UPC #:783126056730
Inventory
Attributes
Features
Documentation
Attributes
Brand:O-Z/Gedney
Type:Type EY 25% Fill Female Dust-Ignitionproof Explosionproof Raintight
Size:1/2 in
Suitable For Use With:Threaded IMC/Rigid Metal Conduit
Mounting Type:Surface
Material:Copper-Free Aluminum
Dimensions:2-3/4 in L x 1-3/16 in W
Features
Prevent passage of gases, vapors or flames from one portion of conduit system to another, restrict any explosion to the sealed off enclosure, prevent pressure piling within conduit system |
Required in class I, division 1 and 2 locations within 18 in of enclosures containing apparatus that may cause arcs, sparks or high temperatures |
Required in class I, division 1 and 2 locations where 2 in or larger conduit enters enclosure, fitting housing terminals, splices or taps |
Required in class I, division 1 and 2 locations at the boundary where conduit leaves classified location |
Required in class I, division 1 and 2 locations where two or more enclosures are connected by 36 in or less conduit, seal must be located within 18 in of either enclosure |
Required where cables (which exceed rate of gas or vapor transmission permitted for seals) are used in class I, division 2 locations |
Smooth, rounded integral bushing in each hub to protect conductor insulation |
Accurately tapped, tapered threads for tight, rigid joints and ground continuity |
Removable nipple in male sealing fitting may be used interchangeably in top or bottom hub |
UL listed for use with Kwiko™ a sealing compound |