EYD10
Appleton®* Actual product may vary from image
Explosionproof Rigid/IMC Conduit Seal, Type Drain, Turning Radius 3.69 Inch, Trade Size 4 Inch, Connection Type Female, Material Zinc Electroplated Chromate Epoxy Powder Coated Malleable Iron, Mounting Position Vertical, Enclosure Class I Div 1 and 2 Group C D, Class II Div 1 and 2 Group E F G, Class III, Approval UL 886/E10444, CSA C22.2, Size 9.75 Inch L x 5.25 Inch W, Constructional Feature Explosionproof, Dust-Ignitionproof, Raintight, Used On Threaded Rigid/IMC Metal Conduit
Details
MFG PART #:EYD10
McMc Part #:EGSMEYD10
UPC #:781381620864
Inventory
$869.01 E
Details
MFG PART #:EYD10
McMc Part #:EGSMEYD10
UPC #:781381620864
Inventory
Attributes
Features
Documentation
Attributes
Brand:Appleton®
Type:Dust-Ignitionproof Explosionproof Raintight
Series:EYD
Size:4 in
Suitable For Use With:IMC/Threaded Rigid Metallic Conduit
Material:Grayloy-Iron
Finish:Triple Coated
Dimensions:9-3/4 in L x 5-1/4 in W
Features
Smooth, rounded integral bushing in each hub to protect conductor insulation |
Accurately tapped, tapered NPT threads for tight, rigid joints and ground continuity |
Removable nipple in male sealing fitting may be used interchangeably in top or bottom hub |
Restrict any explosion to the sealed off enclosure |
Required in Class I, Division 1 and 2 locations within 18 in of enclosures containing apparatus that may cause arcs, sparks or high temperatures |
Required in Class I, Division 1 and 2 locations where 2 in or larger conduit enters enclosure, fitting housing terminals, splices or taps |
Required in Class I, Division 1 and 2 locations at the boundary where conduit leaves classified location |
Required in Class I, Division 1 and 2 locations where two or more enclosures are connected by 36 in or less conduit, seal must be located within 18 in of either enclosure |
Required where cables which exceed rate of gas or vapor transmission permitted for seals are used in Class I, Division 2 locations |
Tapered FNPT connection |